| 1. Basic 120 V, 20 A single-phase | 120 V; 20 A; 2.4 kVA nominal | Typically 16–24 outlets; predominantly 5-15R or 5-20R, depending on the design | No built-in metering or switching | Small racks, low-density equipment, or non-critical loads | Confirm receptacle type, input plug, branch-circuit rating, and local continuous-load limits. |
| 2. Metered 208 V, 30 A single-phase | 208 V; 30 A; 6.24 kVA nominal | Often a mix of C13 and C19 outlets; exact outlet count varies by model | Local current or power readings; network reporting varies | Racks needing circuit-level visibility without per-outlet switching | Check metering accuracy, network protocol, alarm thresholds, and outlet compatibility. |
| 3. Metered 208 V, 30 A three-phase | 208 V line-to-line; 30 A; approximately 10.8 kVA balanced nominal | Typically a combination of C13 and C19 outlets distributed across phases | Per-phase current monitoring; advanced models may report voltage and power | Medium-density racks with a three-phase supply | Check phase balance, per-phase limits, input connector, and available fault protection. |
| 4. Switched 208 V, 30 A single-phase | 208 V; 30 A; 6.24 kVA nominal | Commonly C13 and C19 outlets, with individual outlet switching on supported configurations | Remote outlet control, sequencing, and monitoring may be available | Equipment requiring remote reboot or controlled power-up | Verify outlet-level switching, access controls, reboot safeguards, and management-network security. |
| 5. Metered 230 V, 32 A single-phase | 230 V; 32 A; 7.36 kVA nominal | Typically C13 and C19 outlets; outlet mix depends on the connected equipment | Local or networked load monitoring, depending on configuration | Racks using a higher-capacity single-phase supply in 230 V environments | Confirm the supply and connector match the site standard and that the load stays within circuit limits. |
| 6. Metered 400 V, 32 A three-phase | 400 V line-to-line; 32 A; approximately 22.2 kVA balanced nominal | Often a mix of C13 and C19 outlets; distribution across phases is design-dependent | Per-phase monitoring; some configurations also provide outlet-level readings | Higher-density racks with compatible three-phase infrastructure | Check phase-to-neutral output voltage, neutral requirements, phase loading, and equipment input ratings. |
| 7. High-capacity 400 V, 63 A three-phase | 400 V line-to-line; 63 A; approximately 43.6 kVA balanced nominal | May include C13 and C19 outlets and higher-current outlets, as specified for the installation | Typically requires detailed phase monitoring; switching features vary | High-density deployments designed for a suitably rated three-phase feed | Confirm upstream protection, cabling, connector rating, rack thermal limits, and facility capacity with qualified personnel. |